SetAside Type | ||
Total Small Business Set-Aside (FAR 19.5) | ||
Solicitation ID | Solicitation Title | Solicitation Office |
140R8125Q0073 | TSC - DC RAMP TEST & CORONA PROBE | |
Synopsis | ||
TDC Ramp Test Set: Brand name or equivalent specifications. Preferred brand/model: IRIS DC Ramp Test Set Model DCR 60-2 or equal specs: Has 0 to 60 kilo-Volt Direct-Current, negative polarity output capability; Output current 1.0 mili-Ampere; Measures current accurately in the ranges of 1.0 micro-Ampere to 250 micro-amperes; Infinitely adjustable voltage ramp rate from 0 to 2.5 kilovolts per minute; Voltage limiting trip settings; Performs testing in accordance with IEEE 95-2002 standards; USB connection to PC to record test curves (insulation resistance profile vs. applied voltage); Includes: control unit, HV module, USB communication, control, HV & grounding cables, software license .... Read More
|
||
Office Location | Agency Name | Solicitation Base Posting Type |
BUREAU OF RECLAMATION | Combined Synopsis/Solicitation |